Control System & Electrical
PLC modules, HMIs, frequency inverters, contactors, circuit breakers, cables, and control cabinet spares.
Control System Parts for Concrete Batching Plants
Quality replacement parts with factory-direct pricing. Contact us for a complete list.
Available Control System Parts
| Part Name | Common Material | Specifications |
|---|---|---|
| PLC Modules | Siemens / Schneider / Omron | S7-200 / S7-300 |
| Weighing Indicators | Digital, high precision | For cement/aggregate scales |
| Contactors & Relays | Schneider / Chint | AC 220V / 380V |
| Sensors & Switches | Proximity, limit, level | 24V DC |
| Cables & Connectors | Shielded control cable | Custom lengths |
How to Order the Right Parts
To ensure the correct fit, please provide us with:
- Your mixer / plant model (e.g. HZS120, JS2000)
- The part name and quantity needed
- Photos or drawings of the worn part (if available)
- Your plant's serial number or year of manufacture
Need a quote? Send us your plant model and part list — we respond within 4 hours with specifications, material options and factory pricing. WhatsApp: +86 187 6888 8850
Control System Parts FAQ
Can you supply PLC modules for any brand?
We supply PLC modules for Siemens, Schneider and Omron systems commonly used in HZS plants. Provide your module model number.
Do you offer control system upgrades?
Yes, we upgrade old relay-controlled plants to PLC + PC automatic systems. See our control system upgrade guide for details.
What is the lead time for control parts?
Standard parts ship within 7-15 days; custom panels take 20-30 days depending on configuration.
Why does my batching scale drift over the day?
Temperature-driven resistance change in a bad joint or a damp junction box, nine times out of ten. Re-terminate the connections and check the box for water before replacing any load cell.
The VFD trips when the mixer starts — where do I look first?
At the mechanical side. Material build-up on the arms, a seized bearing or a shaft that will not turn by hand all present as an electrical trip. Confirm the mixer turns freely before touching the drive parameters.
Do I need surge protection on the control panel?
If the plant is in an area with regular storms, yes — a surge arrester on the incoming supply is inexpensive compared with a panel rebuild. Also check that the panel earth is a genuine earth and not a connection to structural steel.
How can I test a load cell without a simulator?
Compare signals. Lift each cell's output at the junction box under the same known load and look for one that reads differently or that changes when you flex its cable. A cell that responds to cable movement is a cable or gland problem, not a cell problem.
Weighing drift is usually wiring, not the load cell
A scale that reads 20 kg heavy in the morning and correct by afternoon sends most people straight to the load cells. Before that, look at the cable. Load cell signals are millivolts — a few tens of millivolts across the bridge — and a joint with a little corrosion in it adds resistance that changes with temperature. That is exactly the behaviour you are seeing.
The usual suspects, in order: a junction box with water in it, a screen that is grounded at both ends and now carries a circulating current, a load cell cable that was extended with ordinary instrument wire rather than the correct screened cable, and a summing board with verdigris on the terminals. Any of these will hold calibration for a while and then drift. All of them are cheaper to fix than a set of load cells.
When the drift is sudden rather than gradual, suspect a single load cell in the group. Lift the signal from each cell in turn at the junction box and watch the reading — a cell that has taken a surge or swallowed water will behave differently from the other two under the same load.
Electrical faults and where they start
| Fault | Likely cause | First check |
|---|---|---|
| Weight drifts with temperature | Junction box moisture or bad joint | Open the box, look for water and green terminals |
| Erratic weight on one scale | Single load cell failing | Compare individual cell signals under load |
| VFD trips on mixer start | Mechanical load before electrical fault | Turn the shaft by hand, check for material build-up |
| Panel overheats in summer | Filter mat clogged, no forced air | Filter condition and fan operation |
| Random I/O faults after storm | Surge through signal or supply | Earthing and surge protection on incoming supply |
| Screen freezes or reboots | Supply sagging or loose terminal | Supply voltage under load |
Spares you should keep on the shelf
Plants that run two shifts in remote locations lose days waiting for a proximity switch or a 24 V relay. The parts that stop a batching plant are rarely expensive: proximity switches on the skip and the discharge gates, the contactor and overload for the mixer, the panel cooling fan, and a spare load cell of each capacity used on the plant. Holding those four categories on site costs far less than one lost day of production.
When you order control spares, send the panel drawing or a photograph of the nameplate and the terminal layout. Control systems on Chinese-built HZS and JS plants vary between years even within the same model, and a relay that fits a 2019 panel will not necessarily fit a 2023 one.